84
Function
code
Name
Descriptions
Unit
Factory
setting
Modif.
Setting
range
A6.21
FDT1 lag
0.00~300.00Hz
0.01Hz
1.00Hz
○
0~30000
A6.22
FDT2 level
0.00~300.00Hz
0.01Hz
25.00Hz
○
0~30000
A6.23
FDT2 lag
0.00~300.00Hz
0.01Hz
1.00Hz
○
0~30000
A6.24
Virtual terminal
setting
Binary setting
0
:
Disable
1
:
Enable
Unit’s place of LED
:
BIT0~BIT3
:
X1~X4
Ten’s place of LED
:
BIT0~BIT2
:
X5
1
00
○
0~FFH
A6.25
Reserved
A6.25
Reserved
A6.26
Reserved
A6.27
Reserved
A6.28
Functions of
terminal AO1
0
:
No function
1
:
Output frequency
(
0~ Max.
output frequency
)
2
:
Preset frequency
(
0~ Max. output
frequency
)
3
:
Preset frequency
(
After Acc/Dec
)
(
0~ Max. output frequency
)
4
:
Motor speed
(
0~ Max. speed
)
5
:
Output current
(
0~2*Iei
)
6
:
Output current
(
0~2*Iem
)
7
:
Output torque
(
0~3*Tem
)
8
:
Output power
(
0~2*Pe
)
9
:
Output voltage
(
0~1.2*Ve
)
10
:
Bus voltage
(
0~800V
)
11
:
AI1
12
:
AI2
13
:
Reserved
14
:
Reserved
15
:
Percentage of host
(
0~4095
)
1
0
○
0~36