![Kinco CV100 Series Manual Download Page 81](http://html1.mh-extra.com/html/kinco/cv100-series/cv100-series_manual_1967653081.webp)
78
Function
code
Name
Descriptions
Unit
Factory
setting
Modif.
Setting
range
curve 4
A3.20
Actual value
corresponding to
the Min reference
of curve 4
The same as A3.02
0.01%
0.00%
○
0~10000
Group A4
:
Acc/Dec parameters
A4.00
Acc/Dec mode
0
:
Linear Acc/Dec
1
:
S Curve
1
0
×
0~1
A4.01
Acc time 2
0.0~6000.0
0.1S
20.0S
○
0~60000
A4.02
Dec time 2
0.0~6000.0
0.1S
20.0S
○
0~60000
A4.03
Acc time 3
0.0~6000.0
0.1S
20.0S
○
0~60000
A4.04
Dec time 3
0.0~6000.0
0.1S
20.0S
○
0~60000
A4.05
Acc time 4
0.0~6000.0
0.1S
20.0S
○
0~60000
A4.06
Dec time 4
0.0~6000.0
0.1S
20.0S
○
0~60000
A4.07
S curve acceleration
starting time
10.0%~50.0%(Acc time)
A4.07+ A4.08≤90%
0.1%
20.0%
○
100~500
A4.08
S curve acceleration
ending time
10.0%~70.0%(Acc time)
A4.07+ A4.08≤90%
0.1%
20.0%
○
100~800
A4.09
S curve deceleration
starting time
10.0%~50.0%(Dec time)
A4.09+ A4.10
≤
90%
0.1%
20.0%
○
100~500
A4.10
S curve deceleration
ending time
10.0%~70.0%(Dec time)
A4.09+ A4.10
≤
90%
0.1%
20.0%
○
100~800
A4.11
Quick start-stop
selctor
0
:
Disable
1
:
Quick start,normal stop
2
:
Normal start,quick stop
3
:
Quick start,quick stop
1
0
×
0~3
A4.12
Start ACR-P
0.1~200.0
0.1
20.0
○
1~2000
A4.13
Start ACR-I
0.000~10.000S
0.001S
0.200s
○
0~10000
A4.14
Start AVR-P
0.1~200.0
0.1
20.0
○
1~2000
A4.15
Start AVR-I
0.000~10.000S
0.001S
0.200s
○
0~10000
A4.16
Stop ACR-P
0.1~200.0
0.1
20.0
○
1~2000
A4.17
Stop ACR-I
0.000~10.000S
0.001S
0.200s
○
0~10000
A4.18
Stop AVR-P
0.1~200.0
0.1
20.0
○
1~2000
A4.19
Stop AVR-I
0.000~10.000S
0.001S
0.200s
○
0~10000
Group A5
:
Control parameters