75
Function
code
Name
Descriptions
Unit
Factory
setting
Modif.
Setting
range
4
:
Reserved
5
:
Output by PID process
A2.01
Main and auxiliary
reference
frequency
calculation
0
:
+
1
:
-
2
:
MAX
(
Main reference
,
Auxiliary
reference
)
3
:
MIN
(
Main reference
,
Auxiliary
reference
)
1
0
○
0~3
A2.02
UP/DN rate
0.01~99.99Hz/s
0.01
1.00
○
1~9999
A2.03
UP/DN regulating
control
Unit’s place of LED
:
0
:
Save reference frequency upon
power outage
1
:
Not save reference frequency
upon power outage.
Ten’s place of LED
:
0
:
Hold reference frequency at
stop
1
:
Clear reference frequency at stop
Hundred’s place of LED:
0:UP/DN integral time valid
1:UP/DN speed value
1
00
○
0~11H
A2.04
Jog operating
frequency
0.10~50.00Hz
0.01Hz
5.00
○
10~5000
A2.05
Interval of Jog
operation
0.0~100.0s
0.1s
0.0
○
0~1000
A2.06
Skip frequency 1
0.00~300.00Hz
0.01Hz
0.00
×
0~30000
A2.07
Range of skip
frequency 1
0.00~30.00Hz
0.01Hz
0.00
×
0~3000
A2.08
Skip frequency 2
0.00~300.00Hz
0.01Hz
0.00
×
0~30000
A2.09
Range of skip
frequency
0.00~30.00Hz
0.01Hz
0.00
×
0~3000
A2.10
Skip frequency 3
0.00~300.00Hz
0.01Hz
0.00
×
0~30000
A2.11
Range of skip
frequency 3
0.00~30.00Hz
0.01Hz
0.00
×
0~3000
Group A3:Setting curve