60
d0.16 AI1 input
-
10.00
~
10.00V
【
0.00
】
d0.17 AI2 input
-
10.00
~
10.00V
【
0.00
】
d0.18 AI3 input
-
10.00
~
10.00V
【
0.00
】
d0.16
~
d0.18 are used to display the analog input value
before regulation.
d0.19 Percentage of AI1 after
regulation
-100.0%
~
100.0%
【
0.0
】
d0.20 Percentage of AI2 after
regulation
-100.0%
~
100.0%
【
0.0
】
d0.21 Reserved
d0.19
~
d0.21 are used to display the percentage of
analog input after regulation.
d0.22 AO1 output
0.0%
~
100.0%
【
0.0
】
d0.23
Reserved
d0.22
、
d0.23 are used to diplay the percentage of analog
output that corresponding to the full range.
d0.24 Process close-loop
reference
-100.0%
~
100.0%
【
0.0
】
d0.25 Process close-loop
feedback
-100.0%
~
100.0%
【
0.0
】
d0.26 Process close-loop
error
-100.0%
~
100.0%
【
0.0
】
d0.27 Process close-loop
output
-100.0%
~
100.0%
【
0.0
】
d0.28 Temperature of heatsink 1 0.0
~
150.0
℃【
0.0
】
d0.29 Temperature of heatsink 2 0.0
~
150.0
℃【
0.0
】
Temperature of heatsink 1 is the temperature of IGBT
modules. Different IGBT modules have different
over-temperature threshold.
Temperature of heatsink 2 is the temperature of rectifier.
The drive of 30kW or below does not detect this
temperature.
Temperature display range:0
~
100
℃
.Accuracy
:
5
%
d0.30 Total conduction time
0
~
65535 hours
【
0
】
d0.31 Total operating time
0
~
65535 hours
【
0
】
d0.32 Total fan’s operating time
0
~
65535 hours
【
0
】
d0.30
~
d0.32 define the drive’s total conduction
time,operating time and fan’s operating time after
production.
d0.33 ASR controller output
-300.0~300.0%
(Corresponding to
rated torque of motor
d0.34 Reference torque
-300.0~300.0%
(Corresponding to
rated torque of motor
6.20 Group d1
d1.00 Fault record 1
0
~
50
【
0
】
d1.01 Bus voltage of the latest
failure
0
~
999V
【
0
】
d1.02 Actual current of the latest
failure
0.0
~
999.9A
【
0
】
d1.03 Operation frequency of the
latest failure
0.00~300.0Hz
【
0.00
】
d1.04 Operation status of the
latest failure
0
~
FFFFH
【
0000
】
d1.05 Fault record 2
0
~
50
【
0
】
d1.06 Fault record 3
0
~
50
【
0
】
CV100 support 50 kinds of protection alarm and can
record the latest three fault code (d1.00,d1.05,d1.06) and
bus voltage, current,operation frequency and operation
status of the latest fault.
Fault record 1 is the latest fault record.
See Chapter 7 of failure and alarm information during
failures recently occurred for the ease of Trouble
Shooting and repair.
6.21 Group d2
d2.00 Serial number
0~FFFF
【
100
】