74
Function
code
Name
Descriptions
Unit
Factory
setting
Modif.
Setting
range
A1.08
DC injection
braking current at
stop
0.0%~100.0% drive’s rated current
0.1%
0.0%
○
0~1000
A1.09
DC injection
braking time at
stop
0.0
(
No action
)
0.01~30.00s
0.01s
0.00s
○
0~3000
A1.10
Restart after power
failure
0:Disable
1:Enable
1
0
×
0~1
A1.11
Delay time for
restart after power
failure
0.0~10.0s
0.1s
0.0s
○
0~100
A1.12
Anti-reverse
running function
0
:
Disabled
1
:
Enabled (It will operate at zero
frequency when input a reverse
command)
1
0
×
0~1
A1.13
Delay time of run
reverse/forward
0.00~360.00s
0.01s
0.00s
○
0~36000
A1.14
Switch mode of
run
reverse/forward
(
Reserved
)
0
:
Switch when pass 0Hz
1
:
Switch when pass starting
frequency
1
0
×
0~1
A1.15
Detecting
frequency of stop
0.00~150.00Hz
0.01Hz
0.10Hz
×
0~15000
A1.16
Action voltage of
braking unit
650~750V
1
720
×
650~750
A1.17
Dynamic braking
0
:
Disable
1
:
Enable
1
0
×
0~1
A1.18
Ratio of working
time of braking
unit to drive’s total
working time
0.0~100.0
%
0.1%
80.0%
○
0~1000
Group A2
:
Frequency setting
A2.00
Auxiliary
reference
frequency selector
0
:
No auxiliary reference frequency
1
:
AI1
2
:
AI2
3
:
Reserved
1
0
○
0~5