73
Function
code
Name
Descriptions
Unit
Factory
setting
Modif.
Setting
range
A0.09
Max. output
voltage
0~480
1V
VFD’s
rated
values
×
0~480
A0.10
Upper limit of
frequency
A0.12~A0.08
0.01Hz
50.00
○
0~30000
A0.11
Lower limit of
frequency
0.00~A0.11
0.01Hz
0.00
○
0~30000
A0.12
Basic
operating
frequency
0.00~Max.output frequency A0.08
0.01Hz
50.00
○
0~30000
A0.13
Torque boost
0.0%
(
Auto
)
,
0.1%~30.0%
0.1%
0.0%
○
0~300
Group A1
:
Start and stop parameters
A1.00
Starting mode
0 Start from the starting frequency
1 Brake first and then start
2 Start on the fly(including
direction judgement), start at
starting frequency
1
0
×
0~2
A1.01
Starting frequency
0.00~60.00Hz
0.01Hz
0.00Hz
○
0~6000
A1.02
Holding time of
starting frequency
0.00~10.00s
0.01s
0.00s
○
0~1000
A1.03
DC injection
braking current at
start
0.0%~100.0% drive’s rated current
0.1%
0.0%
○
0~1000
A1.04
DC
injection
braking
time at start
0.00
(
No action
)
0.01~30.00s
0.01s
0.00s
○
0~3000
A1.05
Stopping mode
0
:
Dec-to-stop
1
:
Coast-to-stop
2
:
Dec-to-stop+DC injection
braking
1
0
×
0~2
A1.06
DC injection
braking initial
frequency at stop
0.00~60.00Hz
0.01Hz
0.00Hz
○
0~6000
A1.07
Injection braking
waiting time at
stop
0.00~10.00s
0.01s
0.00s
○
0~1000