![Kinco CV100 Series Manual Download Page 31](http://html1.mh-extra.com/html/kinco/cv100-series/cv100-series_manual_1967653031.webp)
28
interval, it will be executed.
A2.06 Skip frequency 1
0.00
~
300.0Hz
【
0.00Hz
】
A2.07 Range of skip
frequency 1
0.00
~
30.00Hz
【
0.00Hz
】
A2.08 Skip frequency 2
0.00
~
300.0Hz
【
0.00Hz
】
A2.09 Range of skip
frequency 2
0.00
~
30.00Hz
【
0.00Hz
】
A2.10 Skip frequency 3
0.00
~
300.0Hz
【
0.00Hz
】
A2.11 Range of skip
frequency 3
0.00
~
30.00Hz
【
0.00Hz
】
A2.06
~
A2.11 define the output frequency that will
cause
resonant with the load, which should be avoided.
Therefore, the drive will skip the above frequency as
shown in Fig. 6-7. Up to 3 skip frequencies can be set.
Fig.6-7 Skip frequency and skip range
6.4 Group A3
A3.00 Reference frequency
curve selection
0000
~
3333H
【
0000
】
A3.01 Max reference of curve 1
A3.03
~
110.0%
【
100.0%
】
A3.02 Actual value
corresponding to the Max
reference of curve 1
0.0%
~
100.0%
【
100.0%
】
A3.03 Min reference of curve 1 0.0%
~
A3.01
【
0.0%
】
A3.04 Actual value
corresponding to the Min
reference of curve 1
0.0%
~
100.0%
【
0.0%
】
A3.05 Max reference of curve 2 A3.07
~
110.0%
【
100.0%
】
A3.06 Actual value
corresponding to the Max
reference of curve 2
0.0%
~
100.0%
【
100.0%
】
A3.07 Min reference of curve 2 0.0%
~
A3. 05
【
0.0%
】
A3.08 Actual value
corresponding to the Min
reference of curve 2
0.0%
~
100.0
%
【
0.0%
】
A3.09 Max reference of curve 3
A3.11
~
110.0%
【
100.0%
】
A3.10 Actual value
corresponding to the Max
reference of curve 3
0.0%
~
100.0%
【
100.0%
】
A3.11 Min reference of curve 3 0.0%
~
A3. 09
【
0.0%
】
A3.12 Actual value
corresponding to the Min
reference of curve 3
0.0%
~
100.0
%
【
0.0%
】
A3.13 Max reference of curve 4
A3.15
~
110.0%
【
100.0%
】
A3.14 Actual value
corresponding to the Max
reference of curve 4
0.0%
~
100.0%
【
100.0%
】
A3.15 Reference of inflection
point 2 of curve 4
A3.17
~
A3.13
【
100.0%
】
A3.16 Actual value
corresponding to the Min
reference of inflection point 2
of curve 4
0.0%
~
100.0%
【
100.0%
】
A3.17 Reference of inflection
point 1 of curve 4
A3.19
~
A3.15
【
0.0%
】
A3.18 Actual value
corresponding to the Min
reference of inflection point 1
of curve 4
0.0%
~
100.0%
【
0.0%
】
A3.19 Min reference of curve 4 0.0%
~
A3. 17
【
0.0%
】
A3.20 Actual value
corresponding to the Min
0.0%
~
100.0%
【
0.0%
】
Skip
Frequency 1
Skip
Frequency 2
Skip
frequency 3
Adjusted preset
frequency
Skip range 1
Skip range 2
Skip range 3
Preset
frequency