www.jouleuk.co.uk | www.joule.ie
92
Victorum Setup – Installer Functions
!
Settings
login
1
2
3
4
5
6
7
8
9
To access the installer functions of the Victorum
unit, navigate to the spanner icon on the home
screen.
Next, scroll to the right to the Settings tile and
press the icon.
Enter the login code to access the installer
functions. The installer code is issued during the
Victorum EAHP installer training program.
Setting the Trickle air flow rate
To set the Trickle air flow rate, press the Settings
icon on the second Settings tile and scroll to the
right to the Trickle Rate setting.
Here the Trickle Rate for the dwelling is set.
The airflow is in m3/hr and can be increased or
decreased in increments of 10, using the plus
and minus buttons.
Once the airflow has been selected, you will be
prompted to save the changes. Pless Yes to
save and No to cancel.
Trickle Rate
-
+
120 m
3 /
hour