www.jouleuk.co.uk | www.joule.ie
30
Victorum EAHP Unit
Electrical Connections
•
The power cable is pre-wired to the Exhaust Air Heat Pump.
•
This Equipment complies with IEC 61000-3-12.
•
If extension of the power cable is required, use the grade H05V2V2-F or equivalent materials.
•
Ensure that main supply connection is made through a switch that disconnects all poles, with
contact gap of a least 3 mm.
•
Devices disconnected from the power supply should be completely disconnected in the
condition of overvoltage category.
•
Keep distances of 20mm or more between power cable and communication cable.
Hz
Volts
Phase
Starting Current
Mains Fuse
HHH-2-0000-VHP
50
230
Single
10A
16A
Communication cable
Option 1
2 Core Flex 0.75mm
2
Option 2
CAT 6a (SFTP), Supplied by Joule
Communications Cable Specifications
Power Specification
During the unit installation first make the ventilation connections, then the
piping connections and then electrical connections. If unit is uninstalled
disconnect the unit in the reverse order.