Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-162-
Function
code
Name
Description
Setting
range
Default Modify
P06.26
AO2 output lower limit
-100.0%
–P06.28
-100.0
–
P06.28
0.0%
○
P06.27
AO2 output corresponding to
lower limit
-10.00V
–10.00V
-10.00
–
10.00
0.00V
○
P06.28
AO2 output upper limit
P06.26
–100.0%
P06.26
–
100.0
100.0%
○
P06.29
AO2 output corresponding to
upper limit
-10.00V
–10.00V
-10.00
–
10.00
10.00V
○
P06.30
AO2 output filter time
0.000s
–10.000s
0.000
–
10.000
0.000s
○
P06.31
AO3 output lower limit
-100.0%
–P06.33
-100.0
–
P06.33
0.0%
○
P06.32
AO3 output corresponding to
lower limit
-10.00V
–10.00V
-10.00
–
10.00
0.00V
○
P06.33
AO3 output upper limit
P06.31
–100.0%
P06.31
–
100.0
100.0%
○
P06.34
AO3 output corresponding to
upper limit
-10.00V
–10.00V
-10.00
–
10.00
10.00V
○
P06.35
AO3 output filter time
0.000s
–10.000s
0.000
–
10.000
0.000s
○
P06.36
HDO output lower limit
-100.0%
–P06.38
-100.0
–
P06.38
-100.00%
○
P06.37
HDO output corresponding
to lower limit
0.00
–50.00kHz
0.00
–50.00
0.0kHz
○
P06.38
HDO output upper limit
P06.36
–100.0%
P06.36
–
100.0
100.0%
○
P06.39
HDO output corresponding
to upper limit
0.00
–50.00kHz
0.00
–50.00 50.00kHz
○
P06.40
HDO output filter time
0.000s
–10.000s
0.000
–
10.000
0.000s
○
P07 group
––Human-machine interface
P07.00
User password
0
–65535
0
–65535
0
○
P07.01
Parameter copy
0: No operation
1: Upload parameters from the
local address to the keypad
2: Download parameters
(including motor parameters)
from the keypad to the local
address
3: Download parameters
(excluding groups P02 and P12)
from the keypad to the local
address
4: Download parameters (only
including groups P02 and P12)
from the keypad to the local
address
0
–4
0
◎