Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-94-
The function codes define the relationship between the output value and analog output. When the output value exceeds
the allowed range, the output uses the lower limit or upper limit.
When the analog output is current output, 1mA equals 0.5V.
In different cases, the corresponding analog output of 100% of the output value is different. See each application for
detailed information.
-100%
100%
Corresponding
setting
AO
-10V
10V
(20mA)
0
AO1, AO2
(-20mA )
P07 group
––Human-machine interface
Function
code
Name
Description
Setting range
Default
P07.00
User password
0
–65535
0
–65535
0
When you set the function code to a non-zero number, password protection is enabled.
If you set the function code to 00000, the previous user password is cleared and password protection is disabled.
After the user password is set and takes effect, you cannot enter the parameter menu if you enter an incorrect password.
Please remember your password and save it in a secure place.
After you exit the function code editing interface, the password protection function is enabled within 1 minute. If password
protection is enabled, "0.0.0.0.0" is displayed when you press the PRG/ESC key again to enter the function code editing
interface. You need to enter the correct user password to enter the interface.
Note: Restoring the default values may delete the user password. Exercise caution when using this function.
Function
code
Name
Description
Setting
range
Default
P07.01
Parameter copy
0: No operation
1: Upload parameters from the local address to
the keypad
2: Download parameters (including motor
parameters) from the keypad to the local address
3: Download parameters (excluding motor
parameters) from the keypad to the local address
4: Download parameters (only including motor
parameters) from the keypad to the local address
0
–4
0
Used to set the parameter copy mode.
Note: After any operation among 1
–4 is complete, the parameter restores to 0. The upload and download
functions are not applicable to group P29.
Function
code
Name
Description
Setting range
Default
P07.02
Function of
QUICK/JOG
0: No function
1: Jog
2: Switch between states
0
–7
1