Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-82-
Function
code
Name
Description
Setting range
Default
setting
14: Switch between combination
setting and A setting
15: Switch between combination
setting and B setting
16: Multi-step speed terminal 1
17: Multi-step speed terminal 2
18: Multi-step speed terminal 3
19: Multi-step speed terminal 4
20: Pause multi-step speed running
21: ACC/DEC time selection 1
22: ACC/DEC time selection 2
23: Simple PLC stop reset
24: Pause simple PLC
25: Pause PID control
26: Reserved
27: Reserved
28: Reserved
29: Disable torque control
30: Disable ACC/DEC
31: Reserved
32: Reserved
33: Clear the frequency
increase/decrease setting temporarily
34: DC braking for stop
35: Switch from motor 1 to motor 2
36: Switch the running command
channel to keypad
37: Switch the running command
channel to terminal
38: Switch the running command
channel to communication
39: Pre-exciting command
40: Clear electricity consumption
41: Keep electricity consumption
42: External fault input 2
43: Enable switching to power
frequency run
44: Switch to the master
45: Switch to the slave
46: Switch-on signal feedback of
rectifier
47
–63: Reserved
This parameter is used to set the corresponding function of digital multi-function input terminals.
Note: Two different multifunction input terminals cannot be configured with a same function.
Setting
Function
Description
0
No function
The VFD does not act even if there is signal input. Set unused
terminals to "no function” to avoid misaction.
1
Run forward
External terminals are used to control the forward/reverse running of
the VFD.
2
Run reversely