Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-131-
Function code
Name
Description
Setting range Default
P18.22
Max. lower bus voltage
recorded by the system
0.0
–3275.0V
0.0
–3275.0
0.0
P18.23
Sum of three phase
currents
0
–65535
0
–65535
0
P18.24
Speed display selection
in vector control
0: Identification speed
1: Ramp reference
0
–1
0
P19 group
––External temperature detection
Function code
Name
Description
Setting range
Default
P19.00
Motor temperature
detection
0: Invalid
1: PT100
2: PTC
3
–4: Reserved
0
–4
0
P19.01
Motor temperature
pre-alarm point
0
℃
–200
℃
0°C
–200°C
(0°C: pre-alarm
invalid)
125°C
P19.02
Motor over-temperature
fault point
0
℃
–200
℃
0°C
–200°C
(0°C: pre-alarm
invalid)
150°C
P19.03
Motor overtemperature
action
0: Report a fault and coast to
stop
1: Keep running without
reporting a fault
2: Stop according to the stop
mode without generating a
fault
0
–2
0
P19.04
Starting temperature of
motor temperature
compensation
0
–60.0
℃
0
–60.0
40.0°C
P19.05
Motor temperature
compensation
coefficient
0.0
–200.0%
0.0
–200.0
100.0%
P19.06
Output voltage
compensation enabling
0: Disabled
1: Enable
0
–1
1
P19.07
Deadzone
compensation regulation
coefficient
0.0
–50.0
0.0
–50.0
1.0
P19.08
Overvoltage stalling
current inner loop Kp
0
–1000
0
–1000
50
P19.09
Overvoltage stalling
current inner loop Ki
0
–1000
0
–1000
250
P19.10
PT100 temperature
display channel
0
–6
0
–6
0.0
P19.11
Temperature of the
channel selected by
P19.10
0.0
–120.0°C
0.0
–120.0
0.0°C