Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-115-
Function
code
Name
Description
Setting range
Default
loss enabled
Tens place:
0: Protection against output phrase
loss disabled
1: Protection against output phrase
loss enabled
The function code is used to enable protection against phase loss.
Function
code
Name
Description
Setting range
Default
P11.01
Frequency drop at
transient power-off
0: Disable
1: Enable
0
–1
0
The function code is used to enable the frequency decrease at sudden power loss.
Function
code
Name
Description
Setting range
Default
P11.02
Frequency drop rate
at transient power-off
0.00Hz/s
–P00.03 (Max. output
frequency)
0.00
–P00.03
1.00Hz/s
If the bus voltage drops to the sudden frequency decreasing point due to the power loss of the grid, the VFD begins to
decrease the running frequency according to P11.02 to make the motor in power generation state. The feedback power
can maintain the bus voltage to ensure the continuous running of the VFD until the recovery of power.
Voltage class
660V
1140V
3300V
Frequency decrease point at sudden
power loss (bus voltage)
700V
1350V
3900V
Note:
1. Adjusting the parameter properly can prevent the stop caused by the VFD protection during shifting the grid.
2. This function can be enabled only when the input phase protection function is disabled.
Function
code
Name
Description
Setting range
Default
P11.03
Overvoltage stalling
protection
0: Disable
1: Enable
0
–1
0
The function code is used to enable the protection against overvoltage stalling.
Overvoltage stall
threshold
Output
frequency
Time t
Time t
DC bus voltage V
Function
code
Name
Description
Setting range
Default
P11.04
Overvoltage stalling
protection voltage
110
–150% (standard bus voltage)
110
–150
125%