Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-174-
Function
code
Name
Description
Setting
range
Default Modify
100.0
P10.21
Running time of step 9
0.0
–6553.5s (m)
0.0
–6553.5
0.0s
○
P10.22
Multi-step speed 10
-100.0
–100.0%
-100.0
–
100.0
0.0%
○
P10.23
Running time of step 10
0.0
–6553.5s (m)
0.0
–6553.5
0.0s
○
P10.24
Multi-step speed 11
-100.0
–100.0%
-100.0
–
100.0
0.0%
○
P10.25
Running time of step 11
0.0
–6553.5s (m)
0.0
–6553.5
0.0s
○
P10.26
Multi-step speed 12
-100.0
–100.0%
-100.0
–
100.0
0.0%
○
P10.27
Running time of step 12
0.0
–6553.5s (m)
0.0
–6553.5
0.0s
○
P10.28
Multi-step speed 13
-100.0
–100.0%
-100.0
–
100.0
0.0%
○
P10.29
Running time of step 13
0.0
–6553.5s (m)
0.0
–6553.5
0.0s
○
P10.30
Multi-step speed 14
-100.0
–100.0%
-100.0
–
100.0
0.0%
○
P10.31
Running time of step 14
0.0
–6553.5s (m)
0.0
–6553.5
0.0s
○
P10.32
Multi-step speed 15
-100.0
–100.0%
-100.0
–
100.0
0.0%
○
P10.33
Running time of step 15
0.0
–6553.5s (m)
0.0
–6553.5
0.0s
○
P10.34
ACC/DEC time of steps 0
–7
of simple PLC
0x0000
–0xFFFF
0x00000
–
0xFFFF
0x0000
○
P10.35
ACC/DEC time of steps 8
–
15 of simple PLC
0x0000
–0xFFFF
0x00000
–
0xFFFF
0x0000
○
P10.36
PLC restart mode
0: Restart from step 1
1: Resume from the paused step
0
–1
0
◎
P10.37
Multi-step time unit
0: second
1: minute
0
–1
0
◎
P11 group
––Protection parameters
P11.00
Protection against phase
loss
0x00
–0x11
Ones place:
0: Protection against input
phrase loss disabled
1: Protection against input
phrase loss enabled
Tens place:
0: Protection against output
phrase loss disabled
1: Protection against output
phrase loss enabled
0x00
–0x11
0x11
○
P11.01
Frequency drop at transient
power-off
0: Disable
1: Enable
0
–1
0
○
P11.02
Frequency drop rate at
transient power-off
0.00Hz/s
–P00.03 (Max.
frequency)/s
0.00
–P00.03 1.00Hz/s
○
P11.03
Overvoltage stalling
protection
0: Disable
1: Enable
0
–1
1
○
P11.04
Overvoltage stalling
110
–150%
(standard
bus
110
–150
125%
○