Goodrive3000 series medium voltage VFD
Goodrive3000 rectifier
-47-
Function
code
Name
Description
Setting
range
Default Modify
P00.04
DC bus voltage setting
method
0: Automatic
1: Keypad
2: Reserved
0
–2
1
◎
P00.05
DC bus voltage setting 300.0
–2100.0V
300.0
–
2100.0V
Model
depended
○
P00.06
–
P00.07
Reserved
●
P00.08
Resonance suppression
factor
0
–10
0
–10
0
●
P00.09 Overmodulation selection
0: Disable
1: Enable
0
–1
1
◎
P00.10
Cooling-fan running
mode
0: Normal mode
1:
Permanent
running
after
power-on
0
–1
0
○
P00.11
Reserved
●
P00.12
Reserved
●
P00.13
Reserved
●
P00.14
Carrier frequency
2.0
–8.0kHz
2.0
–8.0
Model
depended
●
P00.15
Function parameter
restore
0: No operation
1: Restore default values
2: Clear fault records
3: Clear accumulative electricity
consumption
0
–3
0
◎
P00.16
Function parameter
property
0: Invalid
1: Read only
0
–1
0
○
P01 group
—Power-on control and protection
P01.00
Reserved
●
P01.01
Detecting main contactor
actuation feedback
0: Not detect
1: Detect
0
–1
1
◎
P01.02
Undervoltage setting
value of input voltage
75.0
–95.0%
75.0
–95.0
85.0%
●
P01.03
Overvoltage setting value
of input voltage
105.0
–125.0%
105.0
–
125.0
115.0%
●
P01.04
Reserved
●
P01.05
Reserved
●
P01.06
Auto-running wait time 0
–3600.0s
0
–3600.0
0.0s
○
P01.07
Delay of auto fault reset 0.0
–3600.0s
0.0
–3600.0
1.0s
○
P01.08
Auto fault reset count
0
–10
0
–10
0
○
P02 group
––Reserved parameters
P02.00
–
P02.07
Reserved
●
P03 group
––Control parameters
P03.00
–
P03.05
Reserved
●