Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-124-
Function
code
Name
Description
Setting range
Default
P15.02
Received PZD2
0: Disable
1: Set frequency
2: PID reference
3: PID feedback
4: Torque setting
5: FWD rotation upper-limit frequency
setting
6: REV rotation upper-limit frequency
setting
7: Electromotive torque upper limit
8: Braking torque upper limit
9: Virtual input terminal command
10: Virtual output terminal command
11: Voltage setting (special for V/F
separation)
12: AO setting 1
13: AO setting 2
0
–20
0
P15.03
Received PZD3
0
–20
0
P15.04
Received PZD4
0
–20
0
P15.05
Received PZD5
0
–20
0
P15.06
Received PZD6
0
–20
0
P15.07
Received PZD7
0
–20
0
P15.08
Received PZD8
0
–20
0
P15.09
Received PZD9
0
–20
0
P15.10
Received PZD10
0
–20
0
P15.11
Received PZD11
0
–20
0
P15.12
Received PZD12
0
–20
0
The following table describes the second PZD words in the PROFIBUS-DP communication with the master. For the VFD,
the words are received.
Functio
n code
Name
Description
0
Invalid
1
Set frequency
0
–Fmax (Unit: 0.01Hz)
2
PID reference
Range (0
–1000, 1000 corresponds to 100.0%)
3
PID feedback
Range (0
–1000, 1000 corresponds to 100.0%)
4
Torque setting value
Range (-3000
–3000, 1000 corresponds to the 100% of the motor rated
current)
5
FWD rotation upper-limit
frequency setting
0
–Fmax (Unit: 0.01Hz)
6
REV rotation upper-limit
frequency setting
0
–Fmax (Unit: 0.01Hz)
7
Electromotive torque
upper limit
0
–3000, 1000 corresponds to the 100% of the motor rated current
8
Braking torque upper
limit
0
–2000, 1000 corresponding to 100.0% of the motor rated current
9
Virtual input terminal
command
Range: 0x000
–0x1FF
10
Virtual output terminal
command
Range: 0x00
–0x0F
11
Voltage setting
Used for V/F separation, range (0
–1000, 1000 corresponds to 100% of
the motor rated voltage)
12
AO setting 1
Range (-1000
–1000, 1000 corresponds to 100.0%)
13
AO setting 2
Range (-1000
–1000, 1000 corresponds to 100.0%)