Goodrive3000 series medium voltage VFD
PROFIBUS communication
-226-
Function
code
Name
Description
Setting
range
Default
P12.25
DP communication
timeout time
0.0 (invalid), 0.1
–60.0s
0.0
–60.0s
0.0s
Related function codes for inverter unit
Function
code
Name
Description
Setting
range
Default
P15.00
Module type
0: PROFIBUS
0
–1
0
P15.01
PROFIBUS/CANopen
module address
0
–127
0
–127
2
P15.02
Received PZD2
0: Disable
1: Set frequency (0
–Fmax (Unit: 0.01Hz))
2: PID reference (0
–1000, in which 1000
corresponds to 100.0%)
3: PID feedback (0
–1000, in which 1000
corresponds to 100.0%)
4: Torque setting (-3000
–+3000, in which 1000
corresponds to 100.0% of the motor rated current)
5: Setting of the upper limit of forward running
frequency (0
–Fmax, unit: 0.01 Hz)
6: Setting of the upper limit of reverse running
frequency (0
–Fmax, unit: 0.01 Hz)
7: Upper limit of the electromotive torque (0
–3000,
in which 1000 corresponds to 100.0% of the motor
rated current)
8: Upper limit of braking torque (0
–2000, in which
1000 corresponds to 100% of the motor rated
current)
9: Virtual input terminal command. Range: 0x000
–
0x1FF
10: Virtual output terminal command. Range: 0x00
–
0x0F
11: Voltage setting (special for V/F separation)
(0
–1000, in which 1000 corresponds to 100% of the
motor rated voltage)
12: AO output setting 1 (-1000
–+1000, in which
1000 corresponds to 100.0%)
13: AO output setting 2 (-1000
–+1000, in which
1000 corresponds to 100.0%)
0
–20
0
P15.03
Received PZD3
0
–20
0
P15.04
Received PZD4
0
–20
0
P15.05
Received PZD5
0
–20
0
P15.06
Received PZD6
0
–20
0
P15.07
Received PZD7
0
–20
0
P15.08
Received PZD8
0
–20
0
P15.09
Received PZD9
0
–20
0
P15.10
Received PZD10
0
–20
0
P15.11
Received PZD11
0
–20
0
P15.12
Received PZD12
0
–20
0
P15.13
Sent PZD2
0: Invalid
1: Running frequency (*100, Hz)
2: Set frequency (*100, Hz)
3: Bus voltage (*10, V)
4: Output voltage (*1, V)
5: Output current (x10, A)
6: Actual output torque (x10, %)
7: Actual output power (x10, %)
8: Rotation speed of running (x1, RPM)
9: Linear speed of running (x1, m/s)
0
–20
0
P15.14
Sent PZD3
0
–20
0
P15.15
Sent PZD4
0
–20
0
P15.16
Sent PZD5
0
–20
0
P15.17
Sent PZD6
0
–20
0
P15.18
Sent PZD7
0
–20
0
P15.19
Sent PZD8
0
–20
0
P15.20
Sent PZD9
0
–20
0
P15.21
Sent PZD10
0
–20
0
P15.22
Sent PZD11
0
–20
0