Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-114-
The description is as follows:
Function
code
Binary
Step
ACC/DEC
time 1
ACC/DEC T2 ACC/DEC T3 ACC/DEC T4
P10.34
BIT1
BIT0
0
00
01
10
11
BIT3
BIT2
1
00
01
10
11
BIT5
BIT4
2
00
01
10
11
BIT7
BIT6
3
00
01
10
11
BIT9
BIT8
4
00
01
10
11
BIT11
BIT10
5
00
01
10
11
BIT13
BIT12
6
00
01
10
11
BIT15
BIT14
7
00
01
10
11
P10.35
BIT1
BIT0
8
00
01
10
11
BIT3
BIT2
9
00
01
10
11
BIT5
BIT4
10
00
01
10
11
BIT7
BIT6
11
00
01
10
11
BIT9
BIT8
12
00
01
10
11
BIT11
BIT10
13
00
01
10
11
BIT13
BIT12
14
00
01
10
11
BIT15
BIT14
15
00
01
10
11
Select corresponding acceleration/deceleration time, and then convert 16-bit binary number into decimal number, finally,
and then set corresponding function codes.
Function
code
Name
Description
Setting range
Default
P10.36
PLC restart mode
0: Restart from step 1
1: Resume from the paused step
0
–1
0
The function code is used to set the PLC restart mode.
0: Restart from the first step, namely if the VFD stops during running (caused by stop command, fault or power down), it
will run from the first step after restart.
1: Continue running from the step frequency when interruption occurred, namely if the VFD stops during running (caused
by stop command or fault), it will record the running time of current step, and enters this step automatically after restart,
then continue running at the frequency defined by this step in the remaining time.
Function
code
Name
Description
Setting range
Default
P10.37
Multi-step time unit
0: Second
1: Minute
0
–1
0
The function code is used to set the time unit.
0: second; the running time of each step is counted in seconds
1: minute; the running time of each step is counted in minutes
P11 group
––Protection
Function
code
Name
Description
Setting range
Default
P11.00
Protection against
phase loss
0x00
–0x11
Ones place:
0: Protection against input phrase
loss disabled
1: Protection against input phrase
0x00
–0x11
0x11