Goodrive3000 series medium voltage VFD
Goodrive3000 rectifier
-40-
Function
code
Name
Description
Setting range
Default
P11.06
Communication
processing action
0x00
–0x11
Ones place:
0: Respond to write operations
1: Not respond to write operations
Tens place:
0: Reserved
1: Reserved
0x00
–0x11
0x00
The function code is used to select the communication processing action.
0: Respond to write operations. The PWM rectifier responds to both read and write commands from the upper computer.
1: Not respond to write operations. The PWM rectifier does not respond to the write commands, but responds only to the
read commands from the upper computer. This setting can improve the communication efficiency.
Function
code
Name
Description
Setting range
Default
P11.09
CANopen
communication
address
0
–127
0
–127
1
P11.10
CANopen
communication baud
rate
0: 50K BPS
1: 125K BPS
2: 250K BPS
3: 500K BPS
4: 1M BPS
0
–4
3
P11.11
CANopen
communication fault
delay
0.0 (invalid); 0.1
–100.0s
0.1
–100.0
0.0s
P11.12
CANopen
communication
protocol
0: Common control protocol
1: Internal master/salve
communication protocol
0
–1
0
P12 group
––PROFIBUS communication
Function
code
Name
Description
Setting range
Default
P12.00
Module type
0: PROFIBUS
0
–1
0
P12.01
Module address
0
–127
0
–127
2
The function code is used to identify the address of the current PWM rectifier in serial communication.
Note: The option 0 indicates a broadcast address, which means the rectifier only receives and runs the broadcast
commands from the host controller but not respond to the host controller.
Function
code
Name
Description
Setting range
Default
P12.02
Received PZD2
0: Disable
1: DC voltage setting
2
–4: Reserved
5: AO setting 1
6: AO setting 2
7
–13: Reserved
0
–13
0
P12.03
Received PZD3
0
–13
0
P12.04
Received PZD4
0
–13
0
P12.05
Received PZD5
0
–13
0
P12.06
Received PZD6
0
–13
0
P12.07
Received PZD7
0
–13
0
P12.08
Received PZD8
0
–13
0
P12.09
Received PZD9
0
–13
0
P12.10
Received PZD10
0
–13
0