Goodrive3000 series medium voltage VFD
PROFIBUS communication
-224-
Bit
Name
Value sent from slave to master
PZD10
Reserved
Reserved
PZD11
Reserved
Reserved
PZD12
Reserved
Reserved
PZD examples:
Transmission of PZD area is achieved through inverter function code.
Example 1: Reading process data of the VFD
In this example, PZD3 is set to "8: Rotating speed during running" through the VFD parameter P15.14. This operation sets
the parameter forcibly. The setting remains until the parameter is set to another option.
Response (from the VFD to the master station):
PKW1
PKW2
PKW3
PKW4
CW
PZD2
PZD3
…
PZD12
Resp
onse
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
00
0A
...
xx
xx
Example 2: Writing process data into the VFD
In this example, PZD3 is set to "2: same as reference" through the VFD parameter P15.03. The parameter specified in
each request frame is updated with the information contained in PZD3 until another parameter is specified.
Request (from the master station to the VFD):
PKW1
PKW2
PKW3
PKW4
CW
PZD2
PZD3
…
PZD12
Resp
onse
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
00
00
...
xx
xx
Then the content of PZD3 is traction reference within each request frame until a parameter is reselected.
9.5 Fault Information
An EC-TX103 communication card is equipped with two fault indicators. The following figure and table show the indicator
details.
1
2
Figure 9-9 Fault indicators
Table 9-13 Fault indicators
LED No.
Name
Color
Function
1
Online
Green
On--The module is online and data exchange can be performed.
Off--The module is not in the online state.
2
Offline/Fa
ult
Red
On--The module is offline and data exchange cannot be performed.
Off--The module is not in the offline state.
It blinks at the frequency of 1 Hz when a configuration error occurs: