Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-175-
Function
code
Name
Description
Setting
range
Default Modify
protection voltage
voltage)
P11.05
Current limit mode
0x00
–0x11
Ones place: Current limit action
0: Invalid
1: Always valid
Tens place: Hardware current
limit overload alarm
0: Valid
1: Invalid
0x00
–0x11
0x01
◎
P11.06
Automatic current limit
threshold
50.0
–200.0%
50.0
–200.0 150.0%
◎
P11.07
Frequency drop rate during
current limit
0.00
–50.00Hz/s
0.00
–50.00 10.00Hz/s
◎
P11.08
Pre-alarm selection for
VFD/motor OL/UL
0x000
–0x131
Ones place:
0:
Motor
OL/UL
pre-alarm,
relative to the rated motor
current.
1: VFD OL/UL pre-alarm, relative
to the VFD rated current
Tens place:
0: The VFD continues to work for
an OL/UL alarm.
1: The VFD continues to work for
a UL alarm but stops running for
an OL fault.
2: The VFD continues to work for
an OL alarm but stops running
for a UL fault.
3. The VFD stops running for an
OL/UL alarm.
Hundreds place:
0: Detect all the time.
1: Detect during constant speed
running.
0x000
–
0x131
0x000
○
P11.09
Overload pre-alarm
detection threshold
P11.11
–200%
P11.11
–200
150%
○
P11.10
Overload pre-alarm
detection time
0.1
–60.0s
0.1
–60.0
1.0s
○
P11.11
Underload pre-alarm
detection threshold
0%
– P11.09
0
–P11.09
50%
○
P11.12
Underload pre-alarm
detection time
0.1
–60.0s
0.1
–60.0
1.0s
○
P11.13
Fault output terminal action
upon fault occurring
0x00
–0x11
Ones place:
0: Act upon an undervoltage fault
1:
Do
not
act
upon
an
undervoltage fault
0x00
–0x11
0x00
○