Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-185-
Function
code
Name
Description
Setting
range
Default Modify
2: PTC
3: Reserved
4: Reserved
P19.01
Motor temperature pre-alarm
point
0.0°C
–200.0°C
(0.0°C: pre-alarm invalid)
0
–200.0
125.0°
○
P19.02
Motor over-temperature fault
point
0.0
–200.0°
0
–200.0
150.0°
○
P19.03
Motor overtemperature
action
0: Report a fault and coast to
stop
1: Keep running without reporting
a fault
2: Stop according to the stop
mode without generating a fault
0
–2
0
○
P19.04
Starting temperature of
motor temperature
compensation
0
–60.0°C
0
–60.0
40.0°C
○
P19.05
Motor temperature
compensation coefficient
0.0
–200.0%
0.0
–200.0
100.0%
○
P19.06
Output voltage
compensation enabling
0: Disabled
1: Enable
0
–1
1
●
P19.07
Deadzone compensation
regulation coefficient
0.0
–50.0
0.0
–50.0
1.0
●
P19.08
Overvoltage stalling current
inner loop Kp
0
–1000
0
–1000
50
●
P19.09
Overvoltage stalling current
inner loop Ki
0
–1000
0
–1000
250
P19.10
PT100 temperature display
channel
0
–6
0
–6
0.0
●
P19.11
Temperature of the channel
selected by P19.10
0.0
–120.0°C
0.0
–120.0
0.0°C
P20 group
––Encoders
P20.00
Encoder type selection
0: Incremental encoder
1: Reserved
2: Resolver-type encoder
3: Reserved
0
–3
0
◎
P20.01
Encoder pulse count
0
–60000
0
–60000
1024
◎
P20.02
Encoder direction
Ones place: AB direction
0: Forward 1: Reverse
Tens place: Z pulse direction
0: Forward 1: Reverse
0x00
–0x11
0x00
◎
P20.03
Detection time of encoder
offline fault
0.0
–100.0s
0.0
–100.0
0.5s
○
P20.04
Detection time of encoder
reversal fault
0.0
–100.0s
0.0
–100.0
0.8s
○
P20.05
Filter times of encoder
detection
Ones place: Low-speed filter
time
Tens place: High-speed filter
time
0x00
–0x99
0x23
○
P20.06
Speed ratio between motor
and encoder
0.000
–65.535
0.000
–
65.535
1.000
○