Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-146-
"
◎
" indicates that the value of the parameter cannot be modified when the VFD is in running state.
"
●
" indicates that the value of the parameter is detected and recorded, and cannot be modified.
(The VFD automatically checks and constrains the modification of parameters, which helps prevent incorrect
modifications.)
2. The parameters adopt the decimal system (DEC). If the hexadecimal system is adopted, all bits are mutually
independent on data during parameter editing, and the setting ranges at some bits can be hexadecimal (0
–F).
3. "Default" indicates the factory setting of the function parameter. If the value of the parameter is detected or recorded,
the value cannot be restored to the factory setting.
To better protect parameters, the VFD provides the password protection function. After a password is set (that is, P07.00
is set to a non-zero value), "0. 0. 0. 0. 0." is displayed when you press the PRG/ESC key to enter the function code editing
interface. You need to enter the correct user password to enter the interface. For the factory parameters, you need to
enter the correct factory password to enter the interface. (You are not advised to modify the factory parameters. Incorrect
parameter setting may cause operation exceptions or even damage to the VFD.) If password protection is not in locked
state, you can change the password any time. You can set P07.00 to 0 to cancel the user password. When P07.00 is set
to a non-zero value during power-on, parameters are prevented from being modified by using the user password function.
When you modify function parameters through serial communication, the user password protection function is also
applicable and compliant with the same rule.
Function
code
Name
Description
Setting
range
Default Modify
P00 group
––Basic functions
P00.00
Speed control mode
0: SVC mode 0 (for SM)
1: SVC mode 1 (for AM)
2: V/F control
3: Closed-loop vector control
mode (for AM, SM)
Note:
AM-asynchronous motor
SM-synchronous motor
0
–3
2
◎
P00.01
Channel of running
commands
0: Keypad (the indicator is off)
1: Terminal (the indicator blinks)
2: Communication (the indicator
is on)
0
–2
0
○
P00.02
Communication mode of
running commands
0: MODBUS
1: PROFIBUS/CANopen
2: Ethernet
3: Reserved
0
–3
0
○
P00.03
Max. output frequency
P00.04
–400.00Hz
P00.04
–
400.00
50.00Hz
◎
P00.04
Upper limit of running
frequency
P00.05
–P00.03 (Max. frequency)
P00.05
–
P00.03
50.00Hz
◎
P00.05
Lower limit of running
frequency
0.00Hz
–P00.04 (Upper limit of
running frequency)
0.00
–P00.04 0.00Hz
◎
P00.06
Setting channel of A
frequency command
0: Keypad
1: AI1
2: AI2
3: AI3
4: High-speed pulse HDI
5: Simple PLC program
0
–11
0
○