Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-90-
The following table lists the function code options. A same output terminal function can be repeatedly selected.
Setting
Function
Description
0
Invalid
The output terminal does not have any function.
1
Running
Output is valid when there is frequency output during running.
2
Running forward
Output is valid when there is frequency output during forward
running.
3
Running reversely
Output is valid when there is frequency output during reverse
running.
4
Jogging
Output is valid when there is frequency output during jogging.
5
VFD fault
Output is valid when VFD fault occurred.
6
Frequency level detection
FDT1
Refer to the descriptions for P08.32
–P08.33.
7
Frequency level detection
FDT2
Refer to the descriptions for P08.34
–P08.35.
8
Frequency reached
Refer to the description for P08.36.
9
Running at zero speed
Output is valid when the VFD output frequency and reference
frequency are both zero.
10
Upper limit frequency
reached
Output is valid when the running frequency reaches upper limit
frequency.
11
Lower limit frequency
reached
Output is valid when the running frequency reached lower limit
frequency.
12
Ready for running
Main circuit and control circuit powers are established, the
protection functions do not act; when the VFD is ready to run,
output is valid.
13
Pre-exciting
Output is valid during pre-exciting of the VFD.
14
Overload pre-alarm
Output is valid after the pre-alarm detection time elapsed based on
the overload pre-alarm threshold. For details, see the descriptions
for P11.08
–P11.10.
15
Underload pre-alarm
Output is valid after the pre-alarm detection time elapsed based on
the underload pre-alarm threshold. For details, see the
descriptions for P11.11
–P11.12.
16
Simple PLC stage
completed (Reserved)
When the present state of the simple PLC is completed, output is
valid.
17
Simple PLC cycle
completed (Reserved)
When a single cycle of the simple PLC is completed, output is
valid.
18
Reserved
19
Reserved
20
External fault is valid
Output is valid when the external fault (EF) occurs.
21
Reserved
22
Running time reached
The output is valid after the accumulated running time of the VFD
exceeds the time set in P08.27.
23
MODBUS communication
virtual terminal output
Output corresponding signals based on the set value of MODBUS.
Output ON signal when it is set to 1, and output OFF signal when it
is set to 0.
24
POROFIBUS/CANopen
communication virtual
terminal output
Output corresponding signal based on the set value of
PROFIBUS/CANopen; output ON signal when it is set to 1, output
OFF signal when it is set to 0
25
Ethernet communication
virtual terminal output
A signal is output based on the value set through Ethernet
communication. When the value is 1, the ON signal is output; when