Goodrive3000 series medium voltage VFD
Moudbus protocol
-209-
Functio
n code
Name
Description
Setting
range
Default
P11.06
Communication
processing action
0x00
–0x11
Ones place:
0: Respond to write operations
1: Not respond to write operations
Tens place:
0: Reserved
1: Reserved
0x00
–0x11
0x00
8.6.2 Related function codes for Goodrive3000 inverter
Functio
n code
Name
Description
Setting
range
Default
P14.00
Local
communication
address
1
–247; 0 indicates a broadcast address
1
–247
1
P14.01
Communication
baud rate
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
6: 57600BPS
0
–7
4
P14.02
Data bit check
0: No check (N, 8, 1) for RTU
1: Even check (E, 8, 1) for RTU
2: Odd check (O, 8, 1) for RTU
3: No check (N, 8, 2) for RTU
4: Even check (E, 8, 2) for RTU
5: Odd check (O, 8, 2) for RTU
0
–5
1
P14.03
Communication
response delay
0
–200ms
0
–200
5
P14.04
Communication
timeout time
0.0 (invalid); 0.1
–60.0s
0.0
–60.0
0.0s
P14.05
Transmission error
processing
0: Report an alarm and coast to stop
1: Keep running without reporting an alarm
2: Stop in enabled stop mode without reporting an
alarm (applicable only to communication mode)
3: Stop in enabled stop mode without reporting an
alarm (applicable to any mode)
0
–3
0
P14.06
Communication
processing action
Ones place: Action upon the write operation
0: Respond to write operations
1: Not respond to write operations
Tens place: Communication encryption
0: Disabled
1: Enabled
0x00
–0x11
0x00