Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-102-
Function
code
Name
Description
Setting range
Default
2nd-last fault
P07.62
Output terminal status at
2nd-last fault
0
The function codes are used to record display information when the 2nd-last fault occurs. For details, see P07.53
–P07.62.
P08 group
––Enhanced functions
Function
code
Name
Description
Setting range
Default
P08.00
ACC time 2
0.0
–3600.0s
0.0
–3600.0
Model
depended
P08.01
DEC time 2
0.0
–3600.0s
0.0
–3600.0
Model
depended
P08.02
ACC time 3
0.0
–3600.0s
0.0
–3600.0
Model
depended
P08.03
DEC time 3
0.0
–3600.0s
0.0
–3600.0
Model
depended
P08.04
ACC time 4
0.0
–3600.0s
0.0
–3600.0
Model
depended
P08.05
DEC time 4
0.0
–3600.0s
0.0
–3600.0
Model
depended
For details, see P00.11 and P00.12.
The inverter unit has four groups of ACC/DEC time, which can be selected by P05. The factory default ACC/DEC time of
the VFD is the first group.
Function
code
Name
Description
Setting range
Default
P08.06
Running frequency of
jog
0.00
–P00.03 (Max. output frequency)
0.00
–P00.03
5.00Hz
The function code is used to define the reference frequency during jogging.
Function
code
Name
Description
Setting range
Default
P08.07
ACC time for jogging 0.0
–3600.0s
0.0
–3600.0
Model
depended
P08.08
DEC time for jogging 0.0
–3600.0s
0.0
–3600.0
Model
depended
ACC time for jogging means the time needed for the VFD to accelerate from 0Hz to the max. output frequency (P00.03).
DEC time for jogging means the time needed for the VFD to decelerate from the max. output frequency (P00.03) to 0Hz.
Function
code
Name
Description
Setting range
Default
P08.09
Jump frequency 1 0.00
–P00.03 (Max. output frequency)
0.00
–P00.03
0.00Hz
P08.10
Jump frequency
amplitude 1
0.00
–P00.03 (Max. output frequency)
0.00
–P00.03
0.00Hz
P08.11
Jump frequency 2 0.00
–P00.03 (Max. output frequency)
0.00
–P00.03
0.00Hz
P08.12
Jump frequency
amplitude 2
0.00
–P00.03 (Max. output frequency)
0.00
–P00.03
0.00Hz
P08.13
Jump frequency 3 0.00
–P00.03 (Max. output frequency)
0.00
–P00.03
0.00Hz