Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-176-
Function
code
Name
Description
Setting
range
Default Modify
Tens place:
0: Act during automatic reset
1: Do not act during the
automatic reset period
P11.14
Speed deviation detection
value
0.0
–50.0% (determine the speed
deviation at slave torque mode)
0.0
–50.0
10.0%
○
P11.15
Speed deviation detection
time
0.0
–10.0s (No speed deviation
protection for the value=0.0)
0.0
–10.0
0.5s
○
P11.16
Automatic
frequency-reduction during
voltage drop
0: Invalid
1: Valid
0
–1
0
○
P11.17
Overvoltage stalling voltage
loop proportion
0
–60000
0
–60000
60
○
P11.18
Leakage current threshold 0
–2048
0
–2048
0
○
P11.19
Reserved
P11.20
Start frequency of speed
deviation determination
0
–50.00Hz
0
–50.00
5.00Hz
○
P11.21
Reserved
P11.22
Phase loss determination
threshold on input side
1.00
–10.00
1.00
–10.00
1.50
○
P11.23
Reserved
P11.24
Phase loss determination
threshold on AM output
0
–100.0
0
–100.0
50.00
○
P11.25
Rectifier overtemperature
point setting
0
–100.0°C
0
–100.0
85.0°C
○
P11.26
Inverter overtemperature
point setting
0
–100.0°C
0
–100.0
85.0°C
○
P11.27
Time threshold of large DC
determination
0
–10.000s
0
–10.000
5.000s
○
P11.28
Pre-alarm enabling
bit0: Motor OH pre-alarm
enabling
bit1: Overload pre-alarm
enabling
bit2
–bit7: Reserved
0
–255
3
○
P11.29 Overload calculation method
0: Traditional method
1: Integral method
0
–2
0
○
P11.30
Reserved
P12 group
––Parameters of motor 2
P12.00
Type of motor 2
0: Asynchronous motor (AM)
1: Reserved
0
–1
0
◎
P12.01
Rated power of AM 2
0.1
–3000.0kW
0.1
–3000.0
Model
depended
◎
P12.02
Rated frequency of AM 2
0.01Hz
–P00.03 (Max. output
frequency)
0.01
–P00.03 50.00Hz
◎
P12.03
Rated speed of AM 2
1
–36000rpm
1
–36000
Model
depended
◎