Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-151-
Function
code
Name
Description
Default
value
Modify
FWD
REV
COM
K1
K2
Running
command
FWD REV
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Stop
Stop
Forward
running
Reverse
running
2: 3-wire control 1; This mode defines Sin as
enabling terminal, and the running command is
generated by FWD, the direction is controlled by
REV. During running, the Sin terminal should be
closed, and terminal FWD generates a rising edge
signal, then the VFD starts to run in the direction
set by the state of terminal REV; the VFD should
be stopped by disconnecting terminal Sin.
COM
K
SB2
SB1
FWD
REV
SIn
The direction control during running is shown
below.
Sln
REV
Previous
running
direction
Current
running
direction
ON
OFF→
ON
Forward
Reverse
Reverse
Forward
ON
ON→OFF
Reverse
Forward
Forward
Reverse
ON→
OFF
ON
Decelerate to stop
OFF
Sln: 3-wire control, FWD: Forward running, REV:
Reverse running
3: 3-wire control 2; This mode defines Sin as
enabling terminal. The running command is
generated by FWD or REV, and they control the
running direction. During running, the terminal Sin
should be closed, and terminal FWD or REV
generates a rising edge signal to control the
running and direction of VFD; the VFD should be
stopped by disconnecting terminal Sin.