Goodrive350 IP55 High-ingress Protection Series VFD
Basic Operation Instructions
-71-
3. Logic diagram for restart after automatic fault reset
VFD fault
In running
Automatic reset times
of VFD fault<P08.28
Automatic reset
interval of VFD
fault>P08.29
VFD fault reset,
start running
Display fault
code, and stop
N
N
Y
Y
Related parameter list:
Function
code
Name
Description
Default
value
P00.01
Running command channel
0: Keypad
1: Terminal
2: Communication
0
P00.11
Acceleration time 1
0.0
–3600.0s
Depend on
model
P00.12
Deceleration time 1
0.0
–3600.0s
Depend on
model
P01.00
Running mode of start
0: Direct start
1: Start after DC brake
2: Start after speed-track
0
P01.01
Starting frequency of direct
start
0.00
–50.00Hz
0.50Hz
P01.02
Hold time of starting
frequency
0.0
–50.0s
0.0s
P01.03
DC brake current before start 0.0
–100.0%
0.0%
P01.04
DC brake time before start 0.00
–50.00s
0.00s
P01.05
Acceleration/deceleration
mode
0: Straight line
1: S curve
Note:
If mode 1 is selected, it is required to
set P01.07, P01.27 and P01.08
accordingly
0
P01.08
Stop mode
0: Decelerate to stop
1: Coast to stop
0
P01.09
Starting frequency of DC
brake after stop
0.00Hz
–P00.03 (max. output frequency)
0.00Hz