Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-129-
Function
code
Name
Description
Default
value
Modify
: 0.00Hz
output frequency)
Setting range of
: 0.00
–30.00s
: 0.0
–100.0% (of the rated
VFD output current)
Setting range of
: 0.0
–50.0s
P01.13
Deadzone
time of
forward/revers
e rotation
This function code refers to the transition time of
the threshold set by
forward/reverse rotation of the VFD, as shown
below.
Output frequency f
Forward
Reverse
Deadzone
time
Time t
Starting
frequency
Switch over after
zero frequency
Switch over after
starting frequency
Setting range: 0.0
–3600.0s
0.0s
○
P01.14
Forward/rever
se rotation
switch-over
mode
0: Switch over after zero frequency
1: Switch over after starting frequency
2: Switch over after passing stop speed and delay
1
◎
P01.15
Stop speed 0.00
–100.00Hz
0.50Hz
◎
P01.16
Stop speed
detection
mode
0: Set value of speed (the only detection mode
valid in SVPWM mode)
1: Detection value of speed
0
◎
P01.17
Stop speed
detection time
0.00
–100.00s
0.50s
◎
P01.18
Running
protection of
power-on
terminal
When the running command channel is controlled
by terminals, the system will detect running
terminal state automatically during power up.
0: Terminal running command is invalid during
power up. The VFD will not run during power up
even if the running command terminal is detected
to be valid, and the system is in running protection
state. The VFD will run only after this terminal is
cancelled and enabled again.
1: Terminal running command is valid during
power up. The system will start the VFD
automatically after initialization is done if the
running command terminal is detected to be valid
during power up.
Note:
This function must be set with caution,
otherwise, serious consequences may occur.
0
○