Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-179-
Function
code
Name
Description
Default
value
Modify
during running (caused by stop command or fault),
it will record the running time of current step, and
enters this step automatically after restart, then
continue running at the frequency defined by this
step in the remaining time.
P10.37
Multi-step time
unit
0: s; the running time of each step is counted in
seconds;
1: min; the running time of each step is counted in
minutes.
0
◎
P11
––Protection parameters
Function
code
Name
Description
Default
value
Modify
P11.00
Phase-loss
protection
0x000
–0x111
Ones:
0: Disable software input phase loss protection
1: Enable software input phase loss protection
Tens:
0: Disable output phase loss protection
1: Enable output phase loss protection
Hundreds:
0: Disable hardware input phase loss protection
1: Enable hardware input phase loss protection
0x110
○
P11.01
Frequency-dro
p at transient
power down
0: Disable
1: Enable
0
○
P11.02
Energy
braking in
standby state
0: Enable
1: Disable
0
◎
P11.03
Overvoltage
stall protection
0: Disable
1: Enable
Overvoltage stall
threshold
Output
frequency
Time t
Time t
DC bus voltage V
1
○
P11.04
Overvoltage
stall protection
voltage
120
–150% (standard bus voltage) (380V)
136%
○
120
–150% (standard bus voltage) (220V)
120%
P11.05
Current-limit
selection
During accelerated running, as the load is too
large, the actual acceleration rate of motor is lower
0x01
◎