Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-227-
Function
code
Name
Description
Default
value
Modify
P25.26
Upper limit value
of AI3
be adopted during calculation.
When analog input is current input, 0
–20mA
current corresponds to 0
–10V voltage.
In different application cases, 100% of the
analog setting corresponds to different nominal
values.
The figure below illustrates several settings.
-100%
100%
Corresponding
setting
AI
10V
20mA
0
AI3/AI4
Input filter time: Adjust the sensitivity of analog
input, increase this value properly can enhance
the
anti-interference
capacity
of
analog
variables; however, it will also degrade the
sensitivity of analog input.
Note:
AI3 and AI4 can support 0
–10V/0–20mA
input, when AI3 and AI4 select 0
–20mA input,
the corresponding voltage of 20mA is 10V;
Setting range of
: 0.00V
Setting range of
: -300.0%
–300.0%
Setting range of
–10.00V
Setting range of
: -300.0%
–300.0%
Setting range of
: 0.000s
–10.000s
Setting range of
: 0.00V
Setting range of
: -300.0%
–300.0%
Setting range of
–10.00V
Setting range of
: -300.0%
–300.0%
Setting range of
: 0.000s
–10.000s
10.00V
○
P25.27
Corresponding
setting of upper
limit of AI3
100.0%
○
P25.28
Input filter time
of AI3
0.030s
○
P25.29
Lower limit value
of AI4
0.00V
○
P25.30
Corresponding
setting of lower
limit of AI4
0.0%
○
P25.31
Upper limit value
of AI4
10.00V
○
P25.32
Corresponding
setting of upper
limit of AI4
100.0%
○
P25.33
Input filter time
of AI4
0.030s
○
P25.34
HDI3 high-speed
pulse input
function
0: Set input via frequency
1: Count
0
◎
P25.35
Lower limit
frequency of
HDI3
0.000 kHz
0.000
kHz
○
P25.36
Corresponding
setting of lower
limit frequency of
HDI3
-300.0%
–300.0%
0.0%
○
P25.37
Upper limit
–50.000kHz
50.000
○