Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-203-
Function
code
Name
Description
Default
value
Modify
P17.15
Torque reference
value
Relative to percentage of the rated torque of
current motor, display torque reference.
Range:
-300.0%
–300.0%
(rated
motor
current)
0.0%
●
P17.16
Linear speed
0
–65535
0
●
P17.17
Reserved
/
/
/
P17.18
Count value
0
–65535
0
●
P17.19
AI1 input voltage
Display input signal of AI 1
Range: 0.00
–10.00V
0.00V
●
P17.20
AI2 input voltage
Display input signal of AI2
Range: -10.00V
–10.00V
0.00V
●
P17.21
HDIA input
frequency
Display input frequency of HDIA
Range: 0.000
–50.000kHz
0.000
kHz
●
P17.22
HDIB input
frequency
Display input frequency of HDIB
Range: 0.000
–50.000kHz
0.000 kHz
●
P17.23
PID reference
value
Display PID reference value
Range: -100.0
–100.0%
0.0%
●
P17.24
PID feedback
value
Display PID feedback value
Range: -100.0
–100.0%
0.0%
●
P17.25 Motor power factor
Display the power factor of current motor.
Range: -1.00
–1.00
1.00
●
P17.26
Current running
time
Display current running time of the VFD.
Range: 0
–65535min
0min
●
P17.27
Acutal stage of
simple PLC
Displays the present stage of the simple PLC
function.
0
●
P17.28
Motor ASR
controller output
Display the speed loop ASR controller output
value under vector control mode, relative to
the percentage of rated torque of the motor.
Range:
-300.0%
–300.0%
(rated
motor
current)
0.0%
●
P17.29
Pole angle of
open-loop
synchronous motor
Display
initial
identification
angle
of
synchronous motor
Range: 0.0
–360.0
0.0
●
P17.30
Phase
compensation of
synchronous motor
Display phase compensation of synchronous
motor
Range: -180.0
–180.0
0.0
●
P17.31
High-frequency
superposition
current of
synchronous motor
0.0%
–200.0% (rated motor current)
0.0
●
P17.32
Motor flux linkage 0.0%
–200.0%
0.0%
●
P17.33
Exciting current
reference
Display the exciting current reference value
under vector control mode
Range: -3000.0
–3000.0A
0.0A
●