Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-168-
Function
code
Name
Description
Default
value
Modify
Time t
Output frequency f
FDT level
FDT lag
Y1,
RO1, RO2
Time t
: 0.00Hz
output frequency)
Setting range of
: 0.0
–100.0% (FDT1
: 0.00Hz
output frequency)
Setting range of
: 0.0
–100.0% (FDT2
level)
P08.36
Detection value
for frequency
arrival
When the output frequency is within the positive
/negative detection range of the set frequency,
the multi-function digital output terminal outputs
"frequency arrival" signal as shown below.
Y,
RO1, RO2
Output frequency
Set
frequency
Detection amplitude
Time t
Time t
Setting range: 0.00Hz
frequency)
0.00Hz
○
P08.37
Enable/disable
energy-
consumption
brake
0: Disable energy-consumption
1: Enable energy-consumption
1
○
P08.38
Energy-
consumption
brake threshold
voltage
Set
the
starting
bus
voltage
of
energy-consumption brake, adjust this value
properly can brake the load effectively. The
default value will change with the change of
voltage class.
Setting range: 200.0
–2000.0V
220V
voltage:
380.0V;
380V
voltage:
700.0V;
○
P08.39
Running mode
of cooling fan
0: Common running mode
1: The fan keeps running after power up
2. Running mode 2
0
○