Goodrive350 IP55 High-ingress Protection Series VFD
Communication protocol
-291-
Parameter
address
VFD
address
Write
command
CRC
Forward running
03
06
20 00
00 01
42 28
Note:
1. Set the address (P14.00) of the VFD to 03.
2. Set "Channel of running commands" (P00.01) to "Communication", and set "Communication
channel of running commands" (P00.02) to the Modbus/Modbus TCP communication
channel.
3. Click
Send
. If the line configuration and settings are correct, a response transmitted by the
VFD is received as follows:
Parameter
address
VFD
address
Write
command
CRC
Forward running
03
06
20 00
00 01
42 28
9.5 Common communication faults
Common communication faults include the following:
1. No response is returned.
2. The VFD returns an exception response.
Possible causes of no response include the following:
1. The serial port is set incorrectly. For example, the converter uses the serial port COM1, but
COM2 is selected for the communication.
2. The settings of the baud rates, data bits, end bits, and check bits are inconsistent with those
set on the VFD.
3. The positive pole (+) and negative pole (-) of the RS485 bus are connected reversely.
4. The resistor connected to 485 terminals on the terminal block of the VFD is set incorrectly.