Goodrive350 IP55 High-ingress Protection Series VFD
Basic Operation Instructions
-76-
Note:
"/" indicates this multi-function terminal is invalid under present reference channel.
When setting the auxiliary frequency inside the VFD via multi-function terminal UP (10) and
DOWN (11), users can increase/decrease the frequency quickly by setting P08.45 (UP
terminal frequency incremental change rate) and P08.46 (DOWN terminal frequency
decremental change rate).
Sx
Sy
UP terminal
function selection=10
DOWN terminal
function selection=11
UP terminal state
DOWN terminal state
T
F
T
T
UP terminal frequency incremental integral speed P08.45
DOWN terminal frequency decremental integral speed P08.46
Related parameter list:
Function
code
Name
Description
Default
value
P00.03
Max. output frequency
P00.04
–400.00Hz
50.00Hz
P00.04
Upper limit of running
frequency
P00.05
–P00.03
50.00Hz
P00.05
Lower limit of running
frequency
0.00Hz
–P00.04
0.00Hz
P00.06
A frequency command
selection
0: Set via keypad
1: Set via AI1
2: Set via AI2
3: Set via AI3
4: Set via high speed pulse HDIA
5: Set via simple PLC program
6: Set via multi-step speed running
7: Set via PID control
8: Set via Modbus/Modbus TCP
communication
9: Set via PROFIBUS/CANopen/
DeviceNet communication
10: Set via Ethernet communication
11: Set via high speed pulse HDIB
12: Set via pulse train AB
13: Set via
EtherCAT/PROFITNET/Ethernet IP
communication
14: Set via PLC card
15: Reserved
0
P00.07
B frequency command
selection
15