Goodrive350 IP55 High-ingress Protection Series VFD
Basic Operation Instructions
-66-
Related parameter list:
Function
code
Name
Description
Default
value
P00.01
Running command channel
0: Keypad
1: Terminal
2: Communication
0
P00.15
Motor parameter autotuning
0: No operation
1: Rotary autotuning 1; carry out
comprehensive motor parameter
autotuning; rotary autotuning is used in
cases where high control precision is
required;
2: Static autotuning 1 (comprehensive
autotuning); static autotuning 1 is used in
cases where the motor cannot be
disconnected from load;
3: Static autotuning 2 (partial autotuning) ;
when current motor is motor 1, only
P02.06, P02.07 and P02.08 will be
autotuned; when current motor is motor 2,
only P12.06, P12.07 and P12.08 will be
autotuned.
4: Rotary autotuning 2, which is similar to
rotary autotuning 1 but is only applicable to
asynchronous motors.
5: Rotary autotuning 3 (partial autotuning),
which is only applicable to asynchronous
motors.
0
P02.00
Type of motor 1
0: Asynchronous motor
1: Synchronous motor
0
P02.01
Rated power of
asynchronous motor 1
0.1
–3000.0kW
Depend on
model
P02.02
Rated frequency of
asynchronous motor 1
0.01Hz
–P00.03 (max. output frequency)
50.00Hz
P02.03
Rated speed of
asynchronous motor 1
1
–60000rpm
Depend on
model
P02.04
Rated voltage of
asynchronous motor 1
0
–1200V
Depend on
model
P02.05
Rated current of
asynchronous motor 1
0.8
–6000.0A
Depend on
model
P02.06
Stator resistance of
asynchronous motor 1
0.001
–65.535Ω
Depend on
model
P02.07
Rotor resistance of
asynchronous motor 1
0.001
–65.535Ω
Depend on
model
P02.08
Leakage inductance of
asynchronous motor 1
0.1
–6553.5mH
Depend on
model
P02.09
Mutual inductance of
asynchronous motor 1
0.1
–6553.5mH
Depend on