Goodrive350 IP55 High-ingress Protection Series VFD
Basic Operation Instructions
-56-
Function
code
Name
Description
Default
value
P00.00
Speed control mode
0: SVC 0
1: SVC 1
2: SVPWM
3: FVC
Note:
If 0, 1 or 3 is selected, it is required to
carry out motor parameter autotuning first.
2
P00.03
Max. output frequency
P00.04
–400.00Hz
50.00Hz
P00.04
Upper limit of running
frequency
P00.05
–P00.03
50.00Hz
P00.05
Lower limit of running
frequency
0.00Hz
–P00.04
0.00Hz
P00.11
Acceleration time 1
0.0
–3600.0s
Depend on
model
P00.12
Deceleration time 1
0.0
–3600.0s
Depend on
model
P02.00
Type of motor 1
0: Asynchronous motor
1: Synchronous motor
0
P02.02
Rated power of
asynchronous motor 1
0.01Hz
–P00.03 (max. output frequency)
50.00Hz
P02.04
Rated voltage of
asynchronous motor 1
0
–1200V
Depend on
model
P04.00 V/F curve setting of motor 1
0: Straight-type V/F curve
1: Multi-point V/F curve
2: Torque-down V/F curve (power of 1.3)
3: Torque-down V/F curve (power of 1.7)
4: Torque-down V/F curve (power of 2.0)
5: Customized V/F (V/F separation)
0
P04.01
Torque boost of motor 1
0.0%: (automatic) 0.1%
–10.0%
0.0%
P04.02 Motor 1 torque boost cut-off 0.0%
–50.0% (rated frequency of motor 1)
20.0%
P04.03
V/F frequency point 1 of
motor 1
0.00Hz
–P04.05
0.00Hz
P04.04
V/F voltage point 1 of motor
1
0.0%
–110.0%
0.0%
P04.05
V/F frequency point 2 of
motor 1
P04.03
– P04.07
0.00Hz
P04.06
V/F voltage point 2 of motor
1
0.0%
–110.0%
0.0%
P04.07
V/F frequency point 3 of
motor 1
P04.05
– P02.02 or P04.05– P02.16
0.00Hz
P04.08
V/F voltage point 3 of motor
1
0.0%
–110.0%
0.0%
P04.09
V/F slip compensation gain
of motor 1
0.0
–200.0%
100.0%
P04.10
Low-frequency oscillation
control factor of motor 1
0
–100
10