Goodrive350 IP55 High-ingress Protection Series VFD
Basic Operation Instructions
-87-
Set
value
Function
Description
37
Command switches to
terminal
When this terminal is valid, the running command channel
will switch to terminal compulsorily. If this function
becomes invalid, the running command channel will revert
to the original state.
38
Command switches to
communication
When this terminal is valid, the running command channel
will switch to communication compulsorily. If this function
becomes invalid, the running command channel will revert
to the original state.
39
Pre-exciting command
When this terminal is valid, motor pre-exciting will be
started until this terminal becomes invalid.
40
Zero out power consumption
quantity
After this command becomes valid, the power
consumption quantity of the VFD will be zeroed out.
41
Maintain power consumption
quantity
When this command is valid, current operation of the VFD
will not impact the power consumption quantity.
42
Source of upper torque limit
switches to keypad
When this command is valid, the upper limit of the torque
will be set by keypad
43
Position reference point input Valid only for S1, S2, and S3.
44
Disable spindle orientation Spindle orientation is invalid.
45
Spindle zeroing/local position
zeroing
Spindle positioning is triggered.
46
Spindle zero position
selection 1
Spindle zero position selection 1.
47
Spindle zero position
selection 2
Spindle zero position selection 2.
48
Spindle scale division
selection 1
Spindle scale division selection 1.
49
Spindle scale division
selection 2
Spindle scale division selection 2.
50
Spindle scale division
selection 3
Spindle scale division selection 3.
51
Position/speed control
switchover terminal
Terminal for switching between position control and speed
control.
52
Disable pulse input
Pulse input is invalid when the terminal is valid.
53
Clear position deviation
Used to clear the input deviation of position loop.
54
Switch position proportional
gains
Used to switch position proportional gains.
55
Enable cyclic digital
positioning
Cyclic positioning can be enabled when digital positioning
is valid.
56
Emergency stop
When this command is valid, the motor decelerate to
emergency stop as per the time set by P01.26.
57
Motor over-temperature fault
input
Motor stops at motor over-temperature fault input.
59
FVC switches to V/F control
When this terminal is valid in stop state, switch to SVPWM
control.