Goodrive350 IP55 High-ingress Protection Series VFD
Basic Operation Instructions
-82-
Setting
Function
Description
28
AO1 from the Programmable card
0
–1000
29
AO2 from the Programmable card
0
–1000
30
Running speed
0
–Twice the motor rated synchronous
speed.
31
Output torque (bipolar)
0
–Twice the motor rated torque. A
negative value corresponds to 0.0% by
default.
32
AI/AO temperature detection output
AO value of AI/AO temperature
detection
33
–47
Reserved
/
Related parameter list:
Function
code
Name
Description
Default
value
P06.00
HDO output type
0: Open collector high-speed pulse output
1: Open collector output
0
P06.14
AO1 output selection
0: Running frequency (0
–Max. output
frequency)
1: Set frequency (0
–Max. output
frequency)
2: Ramp reference frequency (0
–Max.
output frequency)
3: Rotational speed (0
–Speed
corresponding to max. output frequency)
4: Output current (0
–Twice the VFD rated
current)
5: Output current (0
–Twice the motor
rated current)
6: Output voltage (0
–1.5 times the VFD
rated voltage)
7: Output power (0
–Twice the motor rated
power)
8: Set torque (0
–Twice the motor rated
current)
9: Output torque (Absolute value, 0
–+/-
Twice the motor rated torque)
10: AI1 input (0
–10V/0–20mA)
11: AI2 input (0
–10V)
12: AI3 input (0
–10V/0–20mA)
13: HDIA input(0.00
–50.00kHz)
14: Value 1 set through Modbus/Modbus
TCP (0
–1000)
15: Value 2 set through Modbus/Modbus
TCP (0
–1000)
16: Value 1 set through
0
P06.15
Reserved
0
P06.16
HDO high-speed pulse output
0