Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-172-
Function
code
Name
Description
Default
value
Modify
P08.61
AI3
disconnection
detection
threshold
0
–100%
0
○
P08.62
Output current
filter time
0.000
–10.000s
0.000s
○
P08.63
Output torque
filter times
0
–8
8
○
P09
––PID control
Function
code
Name
Description
Default
value
Modify
P09.00
PID reference
source
When frequency command (
) is
set to 7, or channel of voltage setup (
) is
set to 6, the VFD running mode is process PID
control.
This parameter determines the target reference
channel of process PID.
0: Set by
1: AI1
2: AI2
3: AI3
4: High-speed pulse HDIA
5: Multi-step
6: Modbus/Modbus TCP communication
7: PROFIBUS/CANopen/DeviceNet
communication
8: Ethernet communication
9: High-speed pulse HDIB
10: EtherCAT/PROFITNET/Ethernet IP
communication
11: Programmable expansion card
12: Reserved
The set target value of process PID is relative
value, the set 100% corresponds to 100% of the
feedback signal of controlled system.
The system operates based on the relative value
(0
–100.0%)
0
○
P09.01
PID digital
setting
Users need to set this parameter when
is set to 0, the reference value of this parameter
is the feedback variable of the system.
Setting range: -100.0%
–100.0%
0.0%
○
P09.02
PID feedback
source
This parameter is used to select PID feedback
channel.
0: AI1
1: AI2
0
○