Goodrive350 IP55 High-ingress Protection Series VFD
Basic Operation Instructions
-77-
Function
code
Name
Description
Default
value
P00.08
Reference object of B
frequency command
0: Max. output frequency
1: A frequency command
0
P00.09
Combination mode of setup
source
0: A
1: B
2: (A+B)
3: (A-B)
4: Max (A, B)
5: Min (A, B)
0
P05.01
–
P05.06
Function of multi-function
digital input terminal (S1
–S4,
HDIA, HDIB)
10: Frequency increase (UP)
11: Frequency decrease (DOWN)
12: Clear frequency increase/decrease
setting
13: Switch-over between setup A and
setup B
14: Switch-over between combination
setup and setup A
15: Switch-over between combination
setup and setup B
/
P08.42
Reserved
/
/
P08.43
Reserved
/
/
P08.44
UP/DOWN terminal control
0x000
–0x221
Ones: Frequency enabling selection
0: UP/DOWN terminal setting is valid
1: UP/DOWN terminal setting is invalid
Tens: Frequency control selection
0: Valid only when P00.06=0 or P00.07=0
1: Valid for all frequency modes
2: Invalid for multi-step speed when
multi-step speed takes priority
Hundreds: Action selection at stop
0: Valid
1: Valid during running, clear after stop
2: Valid during running, clear after
receiving stop command
0x000
P08.45
UP terminal frequency
incremental change rate
0.01
–50.00 Hz/s
0.50 Hz/s
P08.46
DOWN terminal frequency
decremental change rate
0.01
–50.00 Hz/s
0.50 Hz/s
P17.00
Set frequency
0.00Hz
–P00.03 (max. output frequency)
0.00Hz
P17.02
Ramps reference frequency 0.00Hz
–P00.03 (max. output frequency)
0.00Hz
P17.14
Digital adjustment value
0.00Hz
–P00.03
0.00Hz