Goodrive350 IP55 High-ingress Protection Series VFD
Basic Operation Instructions
-103-
Before adjustment
After adjustment
Response
Time t
Control long-term vibration:
If the cycle of periodic vibration is longer than the set value of
integral time (Ti), it indicates the integral action is too strong, prolong the integral time (Ti) to
control vibration.
Before adjustment
After adjustment
Time t
Response
Control short-term vibration
: If the vibration cycle is short is almost the same with the set
value of derivative time (Td), it indicates derivative action is too strong, shorten the derivative
time (Td) to control vibration. When derivative time (Td) is set to 0.00 (namely no derivative
control), and there is no way to control vibration, decrease the proportional gain.
Before adjustment
After adjustment
Response
Time t
Related parameter list:
Function
code
Name
Description
Default
value
P09.00
PID reference source
0: Set by P09.01
1: AI1
2: AI2
0