Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-142-
Function
code
Name
Description
Default
value
Modify
P04.01
Torque boost of
motor 1
In order to compensate for low-frequency torque
characteristics, users can make some boost
compensation to the output voltage.
relative to the max. output voltage V
b.
defines the percentage of cut-off
frequency of manual torque boost to the rated
motor frequency f
b.
Torque boost can improve
the low-frequency torque characteristics of V/F.
Users should select torque boost based on the
load, eg, larger load requires larger torque
boost, however, if the torque boost is too large,
the motor will run at over-excitation, which will
cause increased output current and motor
heat-up, thus degrading the efficiency.
When torque boost is set to 0.0%, the VFD is
automatic torque boost.
Torque boost cut-off threshold: Below this
frequency threshold, the torque boost is valid,
exceeding this threshold will nullify torque boost.
Output voltage
Output
frequency
Cut-off
boost
b
f
f
v
v
Setting range of
: 0.0%: (automatic)
0.1%
–10.0%
Setting range of
: 0.0%
–50.0%
0.0%
○
P04.02
Motor 1 torque
boost cut-off
20.0%
○
P04.03
V/F frequency
point 1 of motor
1
When
=1 (multi-point V/F curve), users
can set V/F curve via
V/F curve is usually set according to the
characteristics of motor load.
Note:
V1<V2<V3, f1<f2<f3. If low-frequency
voltage is set too high, motor overheat or
burnt-down may occur, and overcurrent stall or
overcurrent protection may occur to the VFD.
Output voltage
Output
frequency(Hz)
V1
V2
V3
f1
f2
f3
100.0%
b
f
b
V
Setting range of
: 0.00Hz
Setting range of
: 0.0%
–110.0% (rated
0.00Hz
○
P04.04
V/F voltage point
1 of motor 1
00.0%
○
P04.05
V/F frequency
point 2 of motor
1
0.00Hz
○
P04.06
V/F voltage point
2 of motor 1
0.0%
○
P04.07
V/F frequency
point 3 of motor
1
0.00Hz
○
P04.08
V/F voltage point
3 of motor 1
00.0%
○