Goodrive300-01A series VFD for air compressor
Wiring instruction
-20-
Power range (kW)
Terminal screw
specification
Torque of torque driver
(N
·
m)
400
–630
M12
35
Table 3-4 Main circuit terminal description
Terminal
sign
Terminal name
Terminal function
22
–132kW
160kW and higher
R, S, T
Main circuit power input
3PH
AC
input
terminals,
connected to the grid
P1
Reserved
DC reactor terminal 1 P1 and (+) connect to DC
reactor terminals
(+)
Reserved
DC reactor terminal 2
(-)
Reserved
Reserved
PB
None
None
U, V, W
VFD output
3PH AC output terminals,
connected to the motor
Grounding terminal for safety protection
Each
machine
must
be
grounded. The grounding is
implemented through the two
PE terminals on the machine,
and the grounding resistance
is less than
10Ω.