Goodrive300-01A series VFD for air compressor
Function description
-56-
Function
code
Name
Description
Default
Modify
P07.02
Function of
QUICK/JOG
0: No function
1: Jogging
2: Switch display status through the shifting
key
3: Forward/reverse running switching
4: Clear the setting of UP/DOWN
5: Coast to stop
6: Switch running-command giving methods
in sequence
7: Quick debugging mode (non-factory
parameter debugging)
1
◎
P07.03
Sequence of
switching
running-command
channels by
pressing QUICK
0: Keypad→Terminal→Communication
1: Keypad←→Terminal
2: Keypad←→Communication
3: Keypad←→Communication
0
○
P07.04
Stop function
selection of
STOP/RST
0: Valid only for keypad control
1: Valid both for keypad and terminal control
2: Valid both for keypad and communication
control
3: Valid for all control modes
0
○
P07.05
Selection 1 of
parameters
displayed in
running state
0x0000
–0xFFFF
BIT0: Running frequency (Hz on)
BIT1: Set frequency (Hz blinks)
BIT2: Bus voltage (V on)
BIT3: Output voltage (V on)
BIT4: Output current (A on)
BIT5: Running rotating speed (rpm on)
BIT6: Output power (% on)
BIT7: Output torque (% on)
BIT8: PID reference value (% blinks)
BIT9: PID feedback value (% on)
BIT10: Input terminal state
BIT11: Output terminal state
BIT12: Torque setting value (% on)
BIT13
–BIT15: Reserved
0x03FF
○