Goodrive300-01A series VFD for air compressor
Product overview
-10-
Rated values of AC 3PH 520V(-15%)
–690V(+10%) VFDs
Model
Output power
(kW)
Input current
(A)
Output current
(A)
GD300-01A-022G-6-E
22
35
27
GD300-01A-030G-6-E
30
40
35
GD300-01A-037G-6-E
37
47
45
GD300-01A-045G-6-E
45
52
52
GD300-01A-055G-6-E
55
65
62
GD300-01A-075G-6-E
75
85
86
GD300-01A-090G-6-E
90
95
98
GD300-01A-110G-6-E
110
118
120
GD300-01A-132G-6-E
132
145
150
GD300-01A-160G-6-E
160
165
175
GD300-01A-185G-6-E
185
190
200
GD300-01A-200G-6-E
200
210
220
GD300-01A-220G-6-E
220
230
240
GD300-01A-250G-6-E
250
255
270
GD300-01A-280G-6-E
280
286
300
GD300-01A-315G-6-E
315
334
350
GD300-01A-350G-6-E
350
360
380
GD300-01A-400G-6-E
400
411
430
GD300-01A-500G-6-E
500
518
540
GD300-01A-560G-6-E
560
578
600
GD300-01A-630G-6-E
630
655
680
Note:
Input current of 22
–350kW VFD models is the actually measured result under 660V input
voltage without DC reactor and input/output reactor.
Input current of 400
–630kW VFD models is the actually measured result under 660V input
voltage with input reactor.
Rated output current is defined as the output current under 660V output voltage.
Under the allowable input voltage range, the output current shall not exceed its rated output
current, and the output power also shall not exceed its rated output power.
Summary of Contents for GD300-01A