Goodrive300-01A series VFD for air compressor
Fault information and fault handling
-107-
P19.13
State type
Possible cause
Solution
BIT9=1
Temperature
pre-alarm
Actual temperature detected
by PT1 is higher than the
pre-alarm temperature set
by P18.19.
• Check whether fan control
parameters are set
correctly.
• Whether the fan operates
normally.
• Fan power is too small to
dissipate heat effectively.
• Check whether there is
lubricating oil.
BIT10=1
Pressure alarm
Actual voltage detected by
P1 is larger than the alarm
voltage set by P18.18.
• Check whether solenoid
valve is normal.
• Check whether pressure
control parameters are set
correctly.
BIT11=1
Temperature alarm
Actual temperature detected
by PT1 is higher than the
alarm temperature set by
P18.20.
• Check whether fan control
parameters are correct.
• Whether
fan
operates
normally.
• Fan power is too small to
dissipate heat effectively.
• Check whether there is
lubricating oil.
BIT12=1
Pressure signal
fault
The actual voltage is
detected by P1 to be less
than 1V.
• Pressure detection sensor
is abnormal.
• Pressure detection input P1
signal wire is disconnected.
• Pressure signal interface
does not select current
signal.
BIT13=1
Temperature signal
fault
PT100 sensor is
disconnected.
• Check whether the wiring of
PT100 is normal.
• Check whether temperature
detection
sensor
is
abnormal.
• Temperature detection input
circuit is abnormal.
BIT14=1
Low-temperature
protection
pre-alarm
The
actual
temperature
detected by PT1 is less than
the
low
temperature
• Temperature
detection
sensor is abnormal.
• Temperature detection input