Goodrive300-01A series VFD for air compressor
Product overview
-6-
Category
Function
Specification
Analog
temperature input
1 input (standard): PTA1/PTB1
1 input (optional): PTA2/PTB2
Resolution: 1
℃
Range: -20
℃~
150
℃
Accuracy error: 3
℃
Analog output
1 output (standard): AO1/GND
0
–10V/0–20mA
Digital input
3 inputs (standard): S1, S2, S3
5 inputs (optional): S4, S5, S6, S7, S8
Common terminal: COM
Max. frequency: 1kHz
Digital output
2 outputs (standard): RO1A/RO1C, RO2A/RO2B/RO2C
4 inputs (optional): RO3A, RO4A, RO5A, RO6A, ROC
Contact capacity: 3A/AC250V, 1A/DC30V
485
communication
1 channel (standard): 485+/485-
Shielding layer grounding PE/CGND
Others
Installation mode
Wall installation, flange installation
Temperature of
running
environment
-10
–+50°C; derating is required if the ambient
temperature exceeds 40°C; derate by 1% for every
increased 1°C
Ingress protection
rating
IP20
Pollution degree
Degree 2
Cooling mode
Forced air cooling
DC reactor
DC reactors are optional parts for 7.5
–11kW VFD models
and can be built into the models;
DC reactors have been built into 15
–110kW VFD models
as standard configuration; DC reactors are optional
parts for 132
–315kW VFD models (AC 380V) and can be
externally connected.
EMC filter
C3 filters have been built into the VFDs as standard
configuration. ECM filter is set to be invalid by default, if it
is necessary to enable it, you can manually plug the
jumper cap in the socket marked J10.